12.5 32 Zone Alarm Mimic Card
Each card (BRD43ZAMC) has 32 bi-coloured LED’s which can be used to display the status of up to
32 Zones. The zone numbers assigned to each LED are configurable and the LED’s will operate in the
following manner for the respective zone statuses:
ZONE STATUS LED STATE LED COLOUR
FIRE ON STEADY RED
DEPENDENCY B FLASH RED
DISABLED ON STEADY YELLOW
FAULT FLASH YELLOW
ALL OTHER OFF n/a
The card will also respond to a lamp test when instigated on the panel to which it is connected.
Figure 82: Zone Indicator Decal
(See LAB1516.doc on the Web for Slip in Label)l
Fit EOL Termination Link
if Last Module
on Comms Bus
In
Out
Address SW
(See Note)
1 2 3 4
ON
C
N
1
C
N
2
RS485 Control
/ 27VDC
Comms In
Top C a r d &
PCB Securing Clips
Bottom Card &
PCB Securing Clips
RS485 Control
/ 27VDC
Comms Out
Figure 83: Zone Alarm Mimic Card Rear View showing connectors and Address Switch
Note: See Section 18 for Addressing Details (SW1)