FIREFINDER SERIES II INSTALLATION, COMMISSIONING &
OPERATION
FireFinder
Fire Alarm Control Panel
Series II AS4428
Installation, Commissioning &
Operation
MAN 2986-1
Page view 0
1 2 3 4 5 6 ... 113 114

Summary of Contents

Page 1 - FireFinder

FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION FireFinder Fire Alarm Control Panel Series II AS4428 Installation, Commissio

Page 2 - ACKNOWLEDGE

Page 5 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION MAIN CPU27VDC(CN16) IN302-6692 302-6692 302-6692EXTERNAL LOOP COMMUN

Page 3

Page 95 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 22 Quick Reference Guides MAIN MENU OPTIONSMENU KEY / FUNCTION KEY (

Page 4

Page 96 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION FireFinderTMQuick ReferenceFUNCTION KEY ( TO ENTER FUNCTION FI

Page 5

FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 23 Statement of Compliance Please PRINT 1. Name of building 2. Address 3.

Page 6 - 1 About This Manual

FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 15. I/We 1. 2. 3. Print Name/s Hereby certify that

Page 7 - 2 System Overview

FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 23.1 Installation Details # Indicate with a number in brackets the number of a

Page 8 - CLIENT PANEL CONFIGURATION

FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 24 Commissioning Test Report This FireFinder Fire Alarm Control Panel is inst

Page 9 - 3 FireFinder Description

FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 24.1 Procedure The following tests are the minimum that shall be performed whe

Page 10 - OPERATION

FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION (h) Alarm zone parameters: Each alarm zone circuit is within the equ

Page 11 - Tap lightly around the

FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION (ii) There are no ‘blind’ spots in the area protected.    (iii) Detectors ar

Page 12 - 4.6 Operational Parameters

FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 25 Battery Capacity Calculation INTRODUCTION The standby power source capa

Page 13

Page 6 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unp

Page 14

FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION POWER SUPPLY & BATTERY CALCULATOR Panel Configuration Iq Calculation Iq

Page 15

FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION Idd= I Alarm ( Ia = Iq + Ida – Idd ) = mA Battery capacity at end

Page 16

FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION EXAMPLE CALCULATION Panel Configuration Iq Calculation Iq Evac Type Iq in

Page 17

FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION Idd= 440 I Alarm ( Ia = Iq + Ida – Idd ) = 769 + 720 – 440 = 1049mA Bat

Page 18 - - + -- + -- +

FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION afp - 791 afp - 792 afp - 1220 afp - 1228 Yuasa NP Series Power-Sonic PS Serie

Page 19

Page 7 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 4.6 Operational Parameters GENERAL Max No of Devices per Loop 126 Max

Page 20 - DBA / MCP

Page 8 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION LED Mimic (RS485) Single twisted shielded cable (No return loop) plus 2

Page 21 - 4.11 Main Board (BRD85MBA)

Page 9 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 4.8.1 Connecting the Mains Earth All earth cabling shall be terminated

Page 22

Page 10 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 5 AMP Power Supply Output Voltage: is set to 27.4 Volts. Mains cable s

Page 23 - 4.13 Main CPU (BRD85CPU)

Page 11 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 4.9 Current Limiter, Fuse Board (BRD85CLFB) The Current Limiter, F

Page 24 - 4.14 Slave CPU (302-669)

Page 12 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 4.10 Brigade / PSU Monitor Board (BRD85BPMB) The Brigade / PSU Mo

Page 25

Page 13 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION Isolate RelayAlarm RelayNO C NC+ -+ -NO C NCBatt Fail Relay( N

Page 26

Page 14 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 4.10.1 Battery Connections (TB1) A FireFinder requires two (2) 12 vol

Page 27

FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION FIRE BRIGADE RESPONSE GUIDE 1. INDICATION (INCOMING FIRE ALARM CONDI

Page 28 - 5 FireFinder Control Panel

Page 15 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 4.10.4 Warning System connections (TB5) Warning systems such as the E

Page 29

Page 16 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 4.11 Main Board (BRD85MBA) The Main Board is the "heart" of

Page 30 - FUNCTION

Page 17 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 4.12 Front Panel Board (302-690) The Front Panel Board provides the b

Page 31 - 6 Functions And Menus

Page 18 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 4.13 Main CPU (BRD85CPU) The Main CPU holds the main central processi

Page 32 - 7 The Main Menu

Page 19 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 4.14 Slave CPU (302-669) The Slave CPU (Central Processing Unit) prov

Page 33 - REMOTE MODULE STATUS

Page 20 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 4.15 Conventional Zone Board (302-671) Under the control of a Slave C

Page 34 - 7.2 Testing Menu

Page 21 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 4.16 Addressable Loop Termination Board (302-735) The Addressable Loo

Page 35 - 8 Main Functions

Page 22 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 4.17 Addressable Loop Termination Board (BRD86DLTB-B) The Addressable

Page 36

Page 23 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 5 FireFinder Control Panel Figure 27: The FireFinder™ Control Panel

Page 37 - SELECT NO

Page 24 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION ACKNOWLEDGE Pressing this key will acknowledge an alarm currently disp

Page 38 - 8.7.1 Forgotten Passwords

FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION TABLE OF CONTENTS Page No. 1 About This Manual ...

Page 39 -  Zone:

Page 25 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION LOOP Press this key followed by a number to select the loop you

Page 40 -  OUTPUT:

Page 26 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION IMPORTANT NOTE: It is strongly recommended that all field programming

Page 41 - SELECT NO:

Page 27 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 7 The Main Menu The MAIN MENU is accessed by pressing MENU. FUNCTIONM

Page 42

Page 28 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION Once the above is selected follow the prompts and enter the; i) I/O c

Page 43 - SENSOR ALARMS 1 OF 5

Page 29 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION Loop 1 Sensor 1 SMOKEL1 S1 Z2 STA

Page 44

Page 30 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 8 Main Functions LEVEL II MAIN FUNCTIONS0: DATE 1: TIME 2: DAYN

Page 45 - 11.1 Ancillary Services

Page 31 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION The type of log, number and totals logged, date and time of

Page 46

Page 32 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 8.6 Function Manual I/O Control Press  To display the Manual I/O Con

Page 47 - CN5 O/P 1-8

Page 33 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 8.7.1 Forgotten Passwords Follow the following process if a password

Page 48 - 302-6770

Page 34 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 8.8 Function Programming Press  To display the Level III Programming

Page 49 - Clear Plastic Clip In Label

FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 8.2 Setting the Function Time Facility ...

Page 50 - Top OverLay

Page 35 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION After scrolling through the groups and entering what I/O GROUPS will b

Page 51

Page 36 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 8.8.5 Manual Call Point (MCP) Press MCP: The operator will be prompt

Page 52 - All Fuses are 1A M205 Style

Page 37 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION Select  (Selecting  presents the PROGRAMMING MENU) then  or  (as s

Page 53 - 11.12 Printer

Page 38 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 9 Incoming Fire Alarm Signal  Will operate the red common LED fire

Page 54 - Paper Cutter

Page 39 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 10 Accessing a Loop, Sensor or Zone LOOP OR SENSOR  From the defau

Page 55 - Replacement Paper Roll

Page 40 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 11 Expanding the FACP with Compatible FireFinder Boards 11.1 An

Page 56 - 27VDC IN

Page 41 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 11.2 Compatible FireFinder Boards Module / Board Part No Fast Fit Ki

Page 57 - 11.13 Agent Release Control

Page 42 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 11.3 16/16 Input / Output Board (302-672) The Input / Output Board is

Page 58

Page 43 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 11.5 16 Way Input Board (302-677) Opto-Inputs: Up to 16 inputs c

Page 59

Page 44 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 11.7 Fire Fan Module (BRD25FCB) The Fire Fan Module has four (4) sepa

Page 60 - SERVICE INHIBIT

FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 13.3 High Level Interface Expander (BRD43SPB) ...

Page 61

Page 45 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 11.9 Zone & General Indicator Card (BRD85GIBB) The General Indica

Page 62 - COMMON FAULT

Page 46 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 11.10 Switch and Indicator Card (BRD25GIB – B) This Card can effectiv

Page 63 - LIFT COVER AND PRESS BUTTON

Page 47 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 11.11 8 Way Sounder Monitor Board (302-7420/1) The 8 way Sounder Moni

Page 64 - TB5TB4TB3

Page 48 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 11.12 Printer Specifications  Printing method: directed impact dot

Page 65 - Solenoid

Page 49 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION Self-Test Mode With power applied (green LED illuminated) push the SE

Page 66 - 11.14 Warning Signs

Page 50 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION HingesLEDPushButtonsPaperPUSHMechanismReleaseButtonNote:Front DoorRemo

Page 67 - BRD 42WTB2-A

Page 51 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 11.12.3 Printer Connections and Jumpering Mounted on the back of the

Page 68

Page 52 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 11.13 Agent Release Control Agent Release control consists of a

Page 69 - LINE FAULT

Page 53 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION  Stage 1 outputs are switched to +24VDC. (FIRE ALARM sign i

Page 70 - Page 65

Page 54 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION  A Zone Fault.  A Fault on the interlock input.  A Fault with a

Page 71

Page 1 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 1 About This Manual 1.1 Introduction This manual contains all the inf

Page 72 - 11.17 EV3000

Page 55 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 11.13.1 Agent Release Module (BRD25ARB-A) The Agent Release Module co

Page 73 - 12 Brigade Devices

Page 56 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 11.13.2 Local Control Station (BRD25ARB-B) The Local Control Station

Page 74 -  IMPORTANT

Page 57 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION Lifting the cover and pressing the MCP starts the manual age

Page 75

Page 58 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION INITIAL AGENT (Yellow) Illuminated when the “Initial“Agent is selected

Page 76

Page 59 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 11.13.3 Agent Release Termination Board (BRD25ATB) LK1Q2SW1U5U9U7U1X1

Page 77

Page 60 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 11.13.4 Interface Wiring Monitored Inputs TB2 1 & 2 Solenoid &

Page 78

Page 61 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 11.14 Warning Signs Description The warning signs are driven by a 2

Page 79

Page 62 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION Configuration – Jumper Settings JP 1 (Continuous / Flashing) JP 2 (Si

Page 80 - 14 SmartTerminal

Page 63 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 11.15 Occupant Warning Systems The EV20, EV40, EV60 and EV120 are com

Page 81

Page 64 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION Control Module When the control switch is in; AUTOMATIC - occupant war

Page 82

Page 2 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 2 System Overview The FireFinder Series II is an Intelligent Analogue

Page 83

Page 65 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION ONEXAMPLE OFSETTING - 30SECS( FACTORY SETTING "0" )AND I/P

Page 84 - 14.2 LCD Screen Format

Page 66 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION EV40 Cabling FireFinderBRIGADEPSU MONBOARD+27VDCNOTE: Ensure F7is 3Amp

Page 85 - A - A + C - C+

Page 67 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 11.16 EV60 / 120 The EV60 & 120 are essentially an EV20 MPU and d

Page 86 - 14.3 Operation

Page 68 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 12 Brigade Devices 12.1 ASE (Vic Metro) Brigade Box The ASE Brigade

Page 87 - 14.4 Setting the Address

Page 69 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 13 Expanding the System through Networking Expanding the system can b

Page 88 - 14.5 Mechanical

Page 70 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 2 WIRE & SHIELDRS422 COMMS OUT2 WIRE & SHIELDRS422 COMMS IN27V

Page 89

Page 71 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 13.2 Communications Extender Board (BRD82LTB) The Communications Exte

Page 90 - 14.7 Specifications

Page 72 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 13.3 High Level Interface Expander (BRD43SPB) Hardware The High Level

Page 91 - ConfigManager

Page 73 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION SmartTerminalCOMMUNICATIONSEXTENDER BOARD2 WIRE & SHIELDRS422 COMM

Page 92

Page 74 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 13.4 Expansion Board (302-688) The Expansion Connection Board is use

Page 93

Page 3 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 2.1 FACP Configuration Examples TYPICAL FRONT DOOR LAYOUT FOR A FULLY

Page 94

Page 75 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 14 SmartTerminal SmartTerminal connects to the FireFinder Fire

Page 95 - HEAD OFFICE

Page 76 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION Controls & Indicators ISOLATEEXTERNALBELL (Yellow) Illuminated

Page 96 - 18 Troubleshooting Chart

Page 77 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION ALARMACK (Red) General fire alarm indicator. The LED will flash until

Page 97 - 19 Address Setting

Page 78 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION Key Switch Controls enable key switch. = OFF, = ON Access level 1

Page 98 - 20 Glossary of Terms

Page 79 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 14.2 LCD Screen Format There are 3 events that can be reported and di

Page 99 - 21 Definitions

Page 80 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION Normal / Default: The format for reporting that everything is normal i

Page 100 - 22 Quick Reference Guides

Page 81 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 14.3 Operation The operation of SmartTerminal can be considered to be

Page 101 - Quick Reference

Page 82 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 14.4 Setting the Address Open the front door; locate the “CONFIG” but

Page 102 -  No 

Page 83 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 14.5 Mechanical SmartTerminal essentially consists of two PCBs; 1. B

Page 103

Page 84 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 14.6 Installation & Cabling The Communications Extender Board (It

Page 104

Page 4 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 3 FireFinder Description The following description does not relate to

Page 105

Page 85 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 14.7 Specifications MECHANICAL Dimensions ABS Cabinet: ( mm ) 195mm (

Page 106 - 24.2 System Information

Page 86 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 14.8 Setting the SmartTerminal Controller Configuration in ConfigMana

Page 107

Page 87 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION In the above example Card 1 & 2;  Are active  Are situated in

Page 108

Page 88 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 15 RS232 Modem / Programming / Debug Interfacing The modem I/O port i

Page 109

Page 89 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 16 List Of Compatible Detectors Conventional Detectors The followin

Page 110

Page 90 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 17 Certification Information The FireFinder™ is designed and manufact

Page 111

Page 91 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 18 Troubleshooting Chart Problem Solution No Mains Power Check mains

Page 112

Page 92 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 19 Address Setting BINARY ADDRESS SETTING (APOLLO) SERIES XP95 - ADDR

Page 113

Page 93 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 20 Glossary of Terms ACF: ANCILLARY CONTROL FACILITY ACKD: ACKNO

Page 114

Page 94 FIREFINDER SERIES II INSTALLATION, COMMISSIONING & OPERATION 21 Definitions Addressable system - a fire alarm and detection