FIREFINDER SERIES II INSTALLATION, COMMISSIONING &
OPERATION
9 Incoming Fire Alarm Signal
Will operate the red common LED fire indicator
Will display location of fire alarm origin on the LCD
Will activate external alarm.
Will activate the internal FACP buzzer.
Will activate any ancillary equipment so programmed.
Will abort any test in progress.
The LCD will always display the first fire alarm signal received in the top section of the LCD. The
lower section of the LCD will also permanently display the most recent zone in alarm. Other essential
fire alarm information and fault or disablement information is available via the
PREVIOUS
and
NEXT
keys. After 30 seconds if no key is pressed the top section of the display will revert to displaying the
first zone in alarm.
L1 S1 Z17 ALARM
5/7/2005 15:12:10
SENSOR ALARMS 1 OF 5
DETECTOR 1 SMOKE
Figure 52: LCD Screen with 5 Devices in Alarm
Note: The displayed information changes to that associated with the device as the PREVIOUS /
NEXT push buttons are pressed. If there is a fault condition or a fire alarm and the buzzer is
sounding, press the ACKNOWLEDGE button to stop it sounding