Ampac FireFinder PLUS Specifications Page 115

  • Download
  • Add to my manuals
  • Print
  • Page
    / 126
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 114
Page 109
FIREFINDER PLUS
(
AUST
)
INSTALLATION
,
COMMISSIONING OPERATION
21 Specifications
Metal SP1M (Europe
Only)
Metal SP8X
Mechanical
Dimensions Cabinet: ( mm )
505 (H) x 407 (W) x 150
(D)
845 (H) x 518.5 (W) x
173(D)
Includes window outer
door
Material 1.2mm Mild Steel 1.2mm Mild Steel
Environmental
Temperature:
Humidity:
IP rating
-5ºC to + 40ºC
25% to 95% non condensing
IP30
Mains Input
Input Voltage:
Protection (Quick Acting Fuse):
5 AMP Supply
18 AMP Supply
Minimum Cable Requirements:
195 - 264VAC
2Amp 3AG Slow Blow
N/A
Not less than 0.75mm²
195 - 264VAC
2A 3AG Slow Blow
5A 3AG Slow Blow
Not less than 0.75mm²
Power Supply
Operating Voltage Range:
Power Supply Ripple Voltage:
Power Supply Output Current:
Imax A
Imax B
Protection
20 - 28.2VDC
<250mV
5.6Amps
3Amps
5.5Amps
Current Limiting
20 - 28.2VDC
<250mV
5.6Amps / 18Amps
Current Limiting
Batteries / Battery Charger
Charger Float Voltage
(Temp compensated):
Approved LPCB Battery:
Battery Type:
Max Battery Capacity:
Max Charger Current Limited:
Battery Supply Current Limited:
Battery Low:
Battery Discharged Cut-off Voltage:
Max Battery Resistance
26.6-28.2VDC
(27.3VDC nom @ 20°C)
Genesis NP24-12R
2x12V Sealed Lead Acid
24AH
1.25A
3A and 2A PTC
<23VDC
<21VDC
0.75
26.6-28.2VDC
(27.3VDC nom @ 20°C)
2x12V Sealed Lead Acid
40AH
2A
3A and 2A PTC
<23VDC
<21VDC
0.43
Panel
Quiescent Current ( QI ) 1 Loop 220mA
Max Number of Zone LEDs: 64 128
Loop
Maximum number of Loops:
Maximum Number of Zones:
Maximum Number of Devices:
Loop Current
Cabling Requirements:
Fault supervision:
4
64
126 / loop
500mA / loop
2 core 1.5 -2.5mm² Max
length 1km
O/C, S/C , over current
8
128
126 / loop
500mA / loop
2 core 1.5 -2.5mm² Max
length 1km
O/C, S/C , over current
Outputs
Supervised Alarm (Current Limited)
Alarm / Fault Relay Contacts
Auxiliary VDC – Protected
Cabling Requirements:
24VDC @ 1A Max O/C, S/C, 10K EOL
24VDC @ 1A
24VDC @ 2A
2 core 1 -2.5mm2 Max length 1km
Inputs
Supervised
Cabling Requirements:
O/C, S/C, 10K EOL
2 core 1 -2.5mm2 Max length 1km
Communications
Add-on Module Internal to FACP
External to FACP
RS485
RS485
Page view 114
1 2 ... 110 111 112 113 114 115 116 117 118 119 120 ... 125 126

Comments to this Manuals

No comments

Blue-white F-462 Polysulfone Molded manuály

Uživatelské manuály a uživatelské příručky pro Senzory Blue-white F-462 Polysulfone Molded.
Poskytujeme 1 manuály pdf Blue-white F-462 Polysulfone Molded ke stažení zdarma podle typů dokumentů: Uživatelský manuál






Další produkty a příručky pro Senzory Blue-white

Modely Typ Dokumentu
F-550 Machined Acrylic Block Uživatelský manuál   Blue-White F-550 Machined Acrylic Block User Manual, 2 stránky
F-410N Machined Acrylic Tube Uživatelský manuál   Blue-White F-410N Machined Acrylic Tube User Manual, 4 stránky
F-420N Machined Acrylic Tube Uživatelský manuál   Blue-White F-420N Machined Acrylic Tube User Manual, 4 stránky
F-430N Machined Acrylic Tube Uživatelský manuál   Blue-White F-430N Machined Acrylic Tube User Manual, 4 stránky
Micro-Flo Uživatelský manuál   Blue-White Micro-Flo User Manual, 14 stránky
F-2000 – Pipe Fittings Uživatelský manuál   Blue-White F-2000 – Pipe Fittings User Manual, 12 stránky
F-2000 – Solvent Weld PVC Tee Fitting Uživatelský manuál   Blue-White F-2000 – Solvent Weld PVC Tee Fitting User Manual, 18 stránky
F-2000 – Sensor Uživatelský manuál   Blue-White F-2000 – Sensor User Manual, 22 stránky
Sonic-Pro S4 Ultrasonic Flowmeters Uživatelský manuál   Blue-White Sonic-Pro S4 Ultrasonic Flowmeters User Manual, 32 stránky
Sonic-Pro Hybrid Ultrasonic Flowmeters Uživatelský manuál   Blue-White Sonic-Pro Hybrid Ultrasonic Flowmeters User Manual, 74 stránky