FIREFINDER PLUS
(
AUST
)
INSTALLATION
,
COMMISSIONING OPERATION
12.17.3 Printer Connections and Jumpering
Mounted on the back of the printer mechanism is the PCB that carries the;
Connectors for interconnection to the Main Board,
Jumper links required to set the programmed print modes; and
Printer 5 volt DC Power Supply.
Figure 118: PCB Layout
Jumper Settings
Designator Jumper State Function
J1
NOT Inserted Selects ESC Commands
Inserted Selects UP Commands
J2 Set as
Default
NOT Inserted Selects ASCII Character Printing Mode
Inserted Selects Chinese Character Printing Mode
J3
NOT Inserted Select Printing by Contrary Direction
Inserted Select printing in the Normal Direction
J7 Set as
Default
Insert the Shorting Clip Between Pins
1 and 2
Selects the 12 X 12 Font
Insert the Shorting Clip Between Pin 2
and 3
Selects the 15 X 16 Font
12.17.4 Printer 5 Volt Power Supply
27 volts DC is taken from Main Board (BRD86MBA) and fed to CN1 of the 5volt Printer Power Supply
Board. It is this board that drops this voltage from 27volts to 5volts for use by the Printer. Mounted to
rear of printer
Figure 119: Printer Power Supply Board Layout