Page 23
FIREFINDER PLUS
(
AUST
)
INSTALLATION
,
COMMISSIONING OPERATION
5 FireFinder PLUS Control Panel
Figure 19: The FireFinder PLUS Control Panel
The LCD is used to display abnormal conditions and for interrogation, control and programming
activities. When the FACP is in its normal state a default screen is displayed.
In access level 2 or higher the backlight shall always be ON. Alarm, Fault and Disable information is
accessed through the Main Menu.
Is the intended area for the Alarm Routing Address Code. This area is not printed on
the Decal.
5.1 System Controls
- Active at access level 1, 2 and 3
This control is used to silence the local buzzer. Pressing this button will silence the panel buzzer,
which sounds whenever there is a fire alarm or fault. The sound for a fire alarm is a steady sound
where as for a fault it is intermittent.
- Active at access level 2 and 3.
When the alarm devices are active (FACP is in the fire condition), activating the control will silence all
alarms excluding the External Alarm device.
Activating the control again, will resound the previously silenced alarm devices.
If a new alarm is recognised whilst in the alarm devices are “silenced”, then all alarm devices shall
sound.
Note: If Delays to Outputs have been configured to investigate the delayed Alarm condition press the
“Next” button and “Enter” button.
#1