Page 117
FIREFINDER PLUS
(
AUST
)
INSTALLATION
,
COMMISSIONING OPERATION
including that the receiver responds to signals from an actuating
device for alarm, tamper, low standby power signals and gives a fault
signal when the supervisory signal condition is absent.
(j) Operation of fault and alarm signals: Fault and alarm conditions
correctly detect and indicate as the correct. alarm zone, operating
other required indicators, and operate relevant outputs of the CIE.

(k) Mimic panel:
A
ll mimic panels, annunciators, etc., operate
correctly.

(l) Alarm zone controls: Alarm test, fault test, isolate and rese
t
facility of each alarm zone operates correctly.

(m) Alarm dependency:
A
larm dependency works correctly and
does not apply to devices listed in Clause 3.3 of AS 1670.1.

(n) CIE response to actuating device operation: Each actuating
device has operated when tested with a medium suitable for the
device type and the alarm has indicated on the FIP and at the tested
device.

(o) Fault response time: The response to a fault does not exceed
100 s for each alarm zone circuit.

(p) Alarm response time:
A
t least one detector in each alarm zone
has been tested and the response to the alarm does not exceed 10 s
or the period specified when dependency on more than one alarm
signal is used.

(q) Supervisory signal response time:
A
t least one supervisor
y
device in each alarm zone circuit has been tested and the response
to the supervisory device does not exceed 100 s.

(r) Alarm acknowledgment facility:
A
larm acknowledgemen
t
facilities operate in accordance with the requirements of Clause 3.2
AS 1670.1.

(s) Occupant warning system:
(i) A fault signal is displayed at the CIE when the circuit wiring at the
last speaker or sounder is short or open circuited.

(ii) Each sounder/speaker operates in accordance with the
requirements of Clause 3.22 of AS 1670.1 and a record of the sound
pressure level has been made.

(t) The external alarm indication: is visible from the main approach
to the building.

(u) Manual call points
(i) Each manual call point operates correctly.

(ii) The activation of manual call points do not cause existing detecto
r
alarm indications to be extinguished.

(iii) Manual call points are not subject to alarm dependency.

(v) Smoke and fire door release: Each door-release device
operates correctly.

(w) Flame detectors
(i) The number and type of flame detectors provide adequate
protection for the area.
