Ampac FireFinder PLUS Specifications Page 72

  • Download
  • Add to my manuals
  • Print
  • Page
    / 96
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 71
Page 66
EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION
12.13.5 Operation
The operation of SmartTerminal can be considered to be in one of three states, these are;
1. Power up - when the SmartTerminal is initialising
2. Normal - when the SmartTerminal address has been set and is communicating with the
FACP, reporting normal / abnormal conditions and controlling the FACP via the front panel
controls
3. Fault where the SmartTerminal is in fault and/or is unable to communicate with the FACP.
Power Up
The LCD displays a message telling the operator SmartTerminal is being powered up and that the
hardware is being initialized. Once the hardware has been successfully initialized set the address
and SmartTerminal should automatically transition to the normal state. Should a failure occur on
power up press the “RESET” button located on the LCD PCB and check the address is correct.
Normal
The Normal state is entered from the “Power-up” or a return from the “Fault” state and is displayed
on the LCD if the SmartTerminal is communicating with the FACP and operating correctly. In this
state the front panel Power indicator is illuminated.
Fault
SmartTerminal enters the Fault state upon;
A hardware failure
LCD module failure or
A loss of communications with the FACP (indicated by the “DIAGNOSTIC” LED not
flashing and the “no communications “ message being displayed)
In a Fault condition the front panel NORMAL indicator is extinguished and the details of the fault are
displayed on the LCD. The FACP will also indicate a fault in a similar manner.
Access levels
There are two levels of access.
Access level 1 only the silence buzzer, previous, next and override front panel controls are
operative. All other controls operate in access level 2.
Access level 2 is entered when the key-switch is in the ENABLED position.
Keyswitch disabled Keyswitch enabled
Figure 93: Keyswitch showing Disabled / Enabled Positions