Ampac FireFinder PLUS Specifications Page 50

  • Download
  • Add to my manuals
  • Print
  • Page
    / 96
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 49
Page 44
EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION
8.8.1 Conv (Conventional) Zone
Press CONV ZONE:
Key in the zone number and enter or change the description (DESC) by pressing
buttons to move the flashing underline or curser. The numeric buttons multiple times to access
characters while at the same time using
EDIT Zx DESC AND TYPE STRINGS
DESC < ZONE >
TYPE<
ALPHA KEYS ARE ACTIVE
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
Figure 63: Zone Description & Type Programming
Press to move to the TYPE field or edit the information.
Press to move between fields use the reciprocal button
By going through all the fields a second screen can also be accessed to show the Output options.
Press to step through these fields.
EDIT ZX BRIGADE OPTIONS AND CONFIG
ALRM: Y/N BELL: Y/N AUX: Y/N SPRK: Y/N
AIF: Y/N
ALARM LED: Y/N CONFIG: LATCHING
Use < or > to change setting
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
Figure 64: Brigade Options
The buttons are used to set the Y/N field, which is the selected Zone that will
activate the Brigade Options ALRM, BELL etc and Config.
EDIT Z CONFIGURATION
CONFIG: LATCHING
Use < or > to change alarm setting
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
Figure 65: Zone Configuration Latching / Non-latching
Use or to change the setting
Configuration settings are Latching, Non-Latching, AVF, Self Reset ( 0 to 99 seconds ). After setting
the Configuration the ZONE I/O GROUPS are programmed.
Page view 49
1 2 ... 45 46 47 48 49 50 51 52 53 54 55 ... 95 96

Comments to this Manuals

No comments