EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION
6.4 Function Menu and Access Levels
Three levels of ACCESS are available via separate passwords so that access to certain facilities can
be restricted (such as the ability to enter new passwords).
Level I: Allows access to indications and controls to investigate and respond to a fire or fault
warning.
Level II: In addition to the level I facilities, quiescent, fire alarm fault warning, disable and test
conditions.
Level III: In addition to the level II facilities, reconfigure specific data or control and maintain
the panel in accordance with the manufacturers’ specifications.
Level IV: In an addition to level III trained and authorised by the manufacturer to repair or
alter the firmware of a panel.
6.4.1 Forgotten Passwords
Follow the following process if a password has been forgotten or misplaced;
Entering 9999 into the password field;
Take note of the 4 digit password number displayed on the screen; then
Contact the AMPAC head office and quote the above number;
A temporary password will be issued and a new password can then be programmed into the FACP.
Note: The temporary password becomes invalid if 9999 is entered again or if the panel is re-
powered after 9999 has been entered.