MAN2995-2 05/09/12 Fire Alarm Control Panel (EN54.2 & 4- 1998) Installation, Commissioning & Operation MAN 2995-2 FireFinder PL
Page 4 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 2.3 FACP Configuration Examples TYPICAL FRONT DOOR LAYOUT FOR A FULLY POPU
Page 5 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 3 FireFinder Plus Description The following description does not relate to
Page 6 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION If a system is required to be expanded beyond eight Slave CPU’s then either
Page 7 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 4 Placing The Basic System Into Operation 4.1 Unpacking Carefully unpack
Page 8 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 4.5 Cable Types and Limitations All System wiring should be installed in a
Page 9 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 4.6 Power Supplies and AC Mains Installation Generally the AC Mains will b
Page 10 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 4.6.2 Connecting 5 AMP Power Supply Output Voltage: 27.4 Volts. FUSE Rati
Page 11 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 4.7 Current Limiter, Fuse Board The Current Limiter, Fuse Board prov
Page 12 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 4.8 Brigade / PSU Monitor Board The Brigade / PSU Monitor Board (BRD86BP
Page 13 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION IsolateRelayAlarmRelayBatt Fail Relay(NormallyEnergised)FaultRelayTo CN20
FIRE BRIGADE RESPONSE GUIDE FIRE BRIGADE RESPONSE GUIDE Responding to a Fire Access Level 1 The and indicators will be illum
Page 14 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 4.8.1 Battery Connections A FireFinder PLUS requires two (2) 12 volt bat
Page 15 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 4.8.3 Monitored Inputs Four independently monitored inputs (TB8) are prov
Page 16 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 4.8.4 Monitored Outputs Four independently monitored and controlled outpu
Page 17 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 4.8.5 Relay Output Connections Five “voltage free” relay outputs (TB2
Page 18 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 4.9 Main Board The Main Board (BRD86MBA) carries the devices for
Page 19 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 4.10 Front Panel Board The Front Panel Board (BRD86FPB) provides the butt
Page 20 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 4.11 Main CPU The Main CPU (BRD86MCPU) holds the main central pro
Page 21 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 4.12 Slave CPU The Slave CPU (BRD86SCPU) provides the interfacing signals
Page 22 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 4.13 Addressable Dual Loop Termination Board The Addressable Dual Loop
Page 23 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 4.13.1 Detector loop Isolator Installation In applications where it i
FIRE BRIGADE RESPONSE GUIDE FIRE BRIGADE RESPONSE GUIDE Disabling a Zone / Device Access Level 2 The following example DISABLES
Page 24 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 5 FireFinder PLUS Control Panel Figure 22: The FireFinder PLUS Control P
Page 25 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION indicating the conditions are still present for resounding. A new Fire Ala
Page 26 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION After selecting the Loop number press this button to enter the device nu
Page 27 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 5.2 System Indicators This LED will be illuminated steady if any fire al
Page 28 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 6 Functions And Menus IMPORTANT NOTE: It is strongly recommended that al
Page 29 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 6.4 Function Menu and Access Levels Three levels of ACCESS are available
Page 30 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 7 The Main Menu The MAIN MENU is accessed by pressing MAIN MENU 0:ALAR
Page 31 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 7.3 Pre-Alarms Pressing Displays all Pre-Alarms on the system ZONE: 1
Page 32 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 7.5 Disables Pressing Displays all Disables on the system. ZONE: 1 Zo
Page 33 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 7.7 Status Pressing Displays the Status of the system STATUS MENU 0:LO
TABLE OF CONTENTS Page No. 1 About This Manual ...
Page 34 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION DISPLAY INPUT/OUTPUT STATUS 0:OUTPUTS 1:INPUTS SELECT NO. AC:2Z
Page 35 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION Network Points: DISPLAY NETWORK POINTS 0:STATUS 1:POWER SUPPLY
Page 36 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION Remote Slave Modules: Select from Network Status Remote Slave Modules, t
Page 37 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 7.8 Tools Pressing allows for the Testing of the following selected fie
Page 38 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 7.9 Setup Pressing Displays the setup for sounders, Zone Delay and Prin
Page 39 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 8 The Function Menu The FUNCTION MENU is accessed by pressing button. A
Page 40 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 8.3 Day/Night Press The DAY-NIGHT SETTINGS screen will appear. Time ent
Page 41 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 8.5 TESTS Press to access the TESTS menu. Note this is an Access Level
Page 42 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 8.6 I/O Press To display the Manual I/O Control menu MANUAL I/O CONTRO
Page 43 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 8.7 Passwords (Level III) Press While in the Main Functions menu and ent
7.4 Faults ... 31 7.5 Disables
Page 44 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 8.8.1 Conv (Conventional) Zone Press CONV ZONE: Key in the zone numbe
Page 45 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION EDIT Z I/O GROUPS GROUP1: GROUP2: GROUP3: GROUP4: GROUP5: GROUP6:
Page 46 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 8.8.3 Input Press INPUT: By following the screen prompts as above Edit
Page 47 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 8.8.9 Extra Devices Detected The FireFinder PLUS LCD will indicate extra
Page 48 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 8.8.10 Mismatch Detected If a mismatch is detected the Normal Default
Page 49 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 9 Incoming Fire Alarm Signal Will operate the red common LED fire ind
Page 50 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 10 Accessing a Loop, Device or Zone LOOP OR DEVICE From the default d
Page 51 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 11 Modem / Programming / Debug Interfacing The modem I/O port is a Dual D
Page 52 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 12 Expanding the FACP with Compatible FireFinder PLUS Boards 12.1 Ancill
Page 53 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 12.3 Expansion Board The Expansion Connection Board (BRD86FEPB) is used t
12.14.1 Indicators and Buttons ... 69 12.14.2 Maintenance ...
Page 54 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 12.4 8 Zone Conventional Board This board (BRD43EZC) has 8 conventional z
Page 55 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 12.5 32 Zone Alarm Mimic Card Each card (BRD43ZAMC) has 32 bi-coloured LE
Page 56 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 12.6 8 Way Switch and Indicator Card This card (BRD25GIB-B) has 8 switch
Page 57 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 12.7 16 Way Input Board The 16 Way Input Board (BRD25SIP) makes provision
Page 58 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 12.8 8 Way Relay Board The Relay Board (BRD25EWRB) provides 8 programmabl
Page 59 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 12.8.2 Remote Relay Board In the remote version the Comms In and Out Term
Page 60 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 12.9 8 Way Sounder Board The Sounder Board (BRD25SOP) expands the number
Page 61 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 12.10 4 Way Fire Fan Module The Fire Fan Module (BRD25FCB) has four (4) s
Page 62 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 12.11 4 Way Fan Termination Board The Fan Termination Board (BRD25FTB
Page 63 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 12.12 Communications Extender Board The Communications Extender Board
Page 1 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 1 About This Manual 1.1 Introduction This manual contains all the informa
Page 64 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 12.13.2 Mechanical SmartTerminal is supplied in an ABS cabinet and consi
Page 65 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 12.13.3 Installation & Cabling SmartTerminal is connected to the FACP
Page 66 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 12.13.5 Operation The operation of SmartTerminal can be considered to be
Page 67 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 12.13.6 SmartTerminal Controls and Indicators All controls, except for t
Page 68 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION No Communication Device Isolate / Disables: If configured
Page 69 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 12.14 Printer Specifications Printing method: directed impact dot matr
Page 70 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION Self-Test Mode With power applied (green LED illuminated) push the SEL bu
Page 71 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION HingesLEDPushButtonsPaperPUSHMechanismReleaseButtonNote:Front DoorRemovedI
Page 72 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 12.14.3 Printer Connections and Jumpering Mounted on the back of the prin
Page 73 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 13 Expanding the System Through Networking Expanding the system can be ac
Page 2 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 2 Introduction 2.1 System Overview The purpose of the FireFinder PLUS Fi
Page 74 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION OUTBUZZERINHIBITBUZZERRS485 EOL+5V0VPRINTER 27VTERMINATION BOARD1NO DE ADD
Page 75 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 13.3 High Level Interface Expander Hardware The High Level Interface
Page 76 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION SmartTerminalCOMMUNICATIONSEXTENDER BOARD2 WIRE & SHIELDRS422 COMMS OU
Page 77 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 14 List of Compatible Devices Conventional Detectors The following range
Page 78 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 15 Certification Information The FireFinder Plus is designed and manufac
Page 79 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 16 Maintenance and Troubleshooting Chart 16.1 Maintenance The FireFinder
Page 80 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 16.2 Troubleshooting FireFinder PLUS Resolution of all suspected fault
Page 81 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 17 Compatible Devices AMPAC Type Code Auto Learn Default Device Type Disp
Page 82 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION Manual Call Points 07h S90 MCP S90 MCP MCP 11Fh Discovery MCP DISC
Page 83 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 18 Address Setting BINARY ADDRESS SETTING (APOLLO) SERIES XP95 - ADDRESS
Page 3 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 2.2 Overview & Key Features The FireFinder PLUS is an Intelligent Anal
Page 84 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 19 Glossary of Terms ACF: ANCILLARY CONTROL FACILITY ACKD: ACKNOWL
Page 85 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 20 Definitions Addressable system - a fire alarm and detection sys
Page 86 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 21 Specifications Metal SP1M (LPCB Approved) Metal SP8X Mechanical Dimen
Page 87 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION Metal SP1X Metal SP16X Mechanical Dimensions Cabinet: ( mm ) 505 (H) x
Page 88 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 22 QUICK REFERENCE GUIDE The following guides; Prompt / assist an expe
Page 89 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION 0832 AMPAC Technologies Ltd 7 Ledgar Road Balcatta, Western Australia,
Page 90 EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION