EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION
4.8.1 Battery Connections
A FireFinder PLUS requires two (2) 12 volt batteries (TB9). The batteries should be placed into the
bottom right hand side of the cabinet. A red and black lead coming from TB1 on the Brigade Board
will be clearly seen in the same area, this lead is to be connected to the batteries red to positive and
black to negative once the system is operating on Mains supply.
Battery size is dependant on system configuration and can vary from 12 AHr to over 100 AHr.
Note: Refer to Ampac’s battery calculation tool to calculate the required battery size.
+27VDC
FROM PSU
TB9 is located on the bottom
right hand side of the board
Battery 2
12Volts
Battery 1
12 Volts
+
-
-
+
N1236
TB9
Figure 11: Battery Connections to the Brigade / PSU Monitor Board
4.8.2 Auxiliary 27 Volt Power
Two (2) 1 Amp outputs are available from TB1 terminals 1+ (plus) and 2- (minus) or 3+ and 4- on the
Brigade Board. It is important to note these outputs are short circuit monitored.
TB1 is located in the middle of the
left hand side of the board
TB1
N1236
2 X LIMITED 2A
AUX POWER
OUTPUTS
AUX OUT1
AUX OUT2
+ -
+ -
Figure 12: Auxiliary 27VDC Power Output