Ampac FireFinder PLUS Specifications Page 66

  • Download
  • Add to my manuals
  • Print
  • Page
    / 96
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 65
Page 60
EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION
12.9 8 Way Sounder Board
The Sounder Board (BRD25SOP) expands the number of sounders that can be used on an FACP
by 8. Each output is of a solid state design, rated at 24VDC / 750mA and requires a 10KΩ End of
Line (EOL) resistor regardless of whether or not a sounder is wired to the circuit.
The sounder board will switch ON the sounders as configured (output off, continuous or pulsed) at
the FACP and supervise the sounders for their open circuit, short circuit & line fault conditions.
Note: Sounder polarity MUST be observed.
TB3
TB2
TB1
SW1
-VE
+VE
SOUNDER 1
-VE+VE
SOUNDER 2
-VE
+VE
SOUNDER 3
-VE
+VE
SOUNDER 4
-VE+VE
SOUNDER 5
-VE+VE
SOUNDER 6
-VE
+VE
SOUNDER 7
-VE
+VE
SOUNDER 8
DC IN
0V
27V
Fit EOL Termination
Link 1 if Last Module
on Comms Bus
Address SW
(See Note)
POWER
CN2
CN1
To Sounders 1 to 4 + / -
To Sounders 5 to 8 + / -
1 2 3 4
ON
TB2
TB1
-VE
+VE
SOUNDER 1
-VE+VE
SOUNDER 2
-VE
+VE
SOUNDER 3
-VE
+VE
SOUNDER 4
-VE+VE
SOUNDER 5
-VE+VE
SOUNDER 6
-VE
+VE
SOUNDER 7
-VE
+VE
SOUNDER 8
To Sounders 1 to 4 + / -
To Sounders 5 to 8 + / -
RS485 Control
Comms In
ON
27VDC Out
CN3
CN4
+
-
TB3
DC IN
0V
27V
POWER
27V
- +
10K EOL
Resistor
27VDC In
RS485 Control
Comms Out
EOL
EOL
EOL
EOL
EOL
EOL
EOL
Figure 85: 8 Way Sounder Board Front View showing connectors and Address Switch
Maximum Current per Output: 750mA.
A +27VDC external power supply feed is required
In addition filtering and protection devices are used to reject transients.
Connections
Terminal/s
Function
TB1 to 2
+ve
-Ve
Sounder 1 to 8
TB3
0V
27V
Power DC IN
Note: See Section 17 for Addressing Details (SW1)