ZONESENSE PLUS
OPERATION & PROGRAMMING
ZONE 1
ZONE 3
ZONE 5
ZONE 7
ZONE 2
ZONE 4
ZONE 6
ZONE 8
ALARM
FAULT / ISOLATE
ZONE 1
ZONE 3
ZONE 2
ZONE 4
ALARM
FAULT / ISOLATE
8 ZONE FACP
4 ZONE FACP
2. Zone Fault / Isolate Amber
Illuminated by;
a fault condition on an individual zone (flashing);
isolating a zone/s, illuminated steady unless in fault, then flashes.
A zone in fault that has already been isolated flashes at a different rate than when only in
fault, the off period is the same with the on period being 3 times that of the fault flash rate.
3.4 Liquid Crystal Display
The panel is fitted with an 8 x 2 LCD. Its primary purpose is to display Zone alarm / fault / isolate
information and prompts for system commands come programming. Alarm, Fault and Isolate
information is accessed through the Main Menu. When the FACP is in its normal state a default
screen will be displayed. Examples of LCD Displays are;
AMPAC
MON 12 : 58
F1 / 2
BATTERY
F1 / 1
CHARGER
Default Screen Fault 1 off 2 Battery Fault Fault 1 off 1 Charger or Power Fault
Note: Some of the following sub-menus will not be available if the facility has not been
installed, eg. Brigade, Relays, Fire Fan, Agent Release, Sounder, and / or Input boards /
cards / modules. If one of the above ancillary facilities has been fitted retrospectively it
must be appropriately programmed into the FACP via the SYSTEM and PROGRAM
MENUS, if not a System Fault will be indicated. Once programmed into the FACP the
ancillary facility is monitored in the normal way. Refer to the SYSTEM and PROGRAM
MENU structure diagrams in the Appendix for more information.
Press ENTER to access MAIN MENU
3.5 Main Menu
The Main Menu consists of;
Level 1
Level 2 Activate Control
Level 3 Enter Password
STATUS
FAULTS
TEST
DISABLES
SYSTEM
PROGRAM
Press the Move Right / Move Left key to move through the menu.
Press Enter to access the sub menus.
Move Right to access STATUS
Page view 7
1 2 3 4 5 6 7 8 9 10 11 12 13 ... 28 29