ZONESENSE PLUS
OPERATION & PROGRAMMING
LED Annunciator Master ( LAM )
This tells the FACP how many LAMs are on the system hence how many to look for. Set the
number by using the Move Down and / or Move Up keys to increment to the desired
number 0 to 8 ( maximum of 8 ).
Code
Code is the National Standard the Panel complies with. This is factory set and can not be
altered.
Back out to the Main Menu using the CANCEL key and move from the SYSTEMS Menu to the
PROGRAM Menu using the Move Right key. When the CANCEL key is pressed the LCD will
display;
SYSTEM
ENABLED
for one second and all the Isolate LED’s will be turned off.
6.3 Program
Reminder: From the Zones Menu use the Move Right key to advance through the PROGRAM
Menu.
Pressing Enter to access the Program Menu will again disable the panel and the LED’s will
illuminate as they did in the Systems Menu.
The PROGRAM Menu consists of;
Zones
Clock
MCP Zone
Outputs
Relays
Fire Fan
Sounders
Indicate
Display
Zone Labels
EOL
Zone S/C
Zones
Press Enter and the Zones Menu will be displayed on the LCD screen. Pressing Enter again
will access the Zones sub menu where first the Move Right and Move Left keys are
used to select the Zone number and the Move Up and
Sample Zone Screens
Move Down keys are used to set the functions within that Zone. The functions
are;
Normal
Normal is selected if the Zone is required to initiate an alarm and latch until reset.
AVF
If AVF, ( Alarm Verification Facility ) is set active a delay and re-sampling period is initiated
to confirm an alarm condition actually exists on that Zone.
LAM
8
CODE
AS4428
ZONE 2
NORMAL
ZONE 4
AVF
ZONE 6
AGENT 1