FIREFINDER NZ
CONFIGURATION MANAGER
7.3 Adding an LCD Mimic
To add an LCD Mimic to the system left click on the mimic icon as shown so that is highlighted. Then
left click on the project area of the centre screen and the mimic will be added.
Figure 67: Adding an LCD Mimic Screen
Note: the Node address has been automatically set, e.g. N2 in the above illustration. To display
an address that has already been set access the LCDR via the “debug “port, go to “Application
Mode” and type in DA.
As the mimic has a number of options as to what it can display the access levels must be set. The
default is Global access which means that all of the zones/devices in the system will be displayed on
the LCD. This may be modified by the user by clicking on the Global access box as shown on the
following page.
7.3.1 Global Access
Global Access refers to the access that any node in the network has to any other node in the same
network and is accessed by right clicking on the Mimic Panel and selecting EDIT NETWORK
PARAMETERS. The access refers to what the LCD will display and also what I/O functions will be
operated on, and what testing is allowed. For stand alone panels the default is set to Global as the
panel has full access to itself. This means for a stand alone panel with global access all of the I/O
functions will be activated and all of the configuration will be displayed as required.
In a network this is selectable for each node in the network.
Selection Buttons: [only available in the Panel screen]
Invert Selection: Selects / de-selects the highlighted panels.
Select None: De-selects all Panels shown on the screen and is of particular use on larger networks.