FIREFINDER NZ
CONFIGURATION MANAGER
5.4 Conventional Modules
Selecting a Conventional Module tab on the Module Data entry Spreadsheet will display the page for
entering the data for that module.
Figure 60: The Conventional Module Settings Page
Circuit: The circuit number is set and cannot be modified.
Zone: The zone number must be a number between 1 and 999.
Description: The description is limited to 33 characters and may contain numbers or characters.
Type: The type of device defaults to normal within the drop down list box.
Type Descr: The type descriptor is automatically entered by the program. This may be modified if
required but it is limited to 6 characters.
Zone Cnfg: The zone configuration column uses a drop down list box to display the options that a
device may be set to; these are Normal, AVF, Self Reset, and Non-latching.
Time Out: This column is the used to enter the time out for the Self Reset configuration. A maximum
of 999 seconds is allowable (60 seconds is considered a norm). An error message will be displayed
if the operator attempts to enter something greater than 999 seconds.
Auxiliary Output: The next column is used to determine if the Alarm LED on the main control panel
is active.
Groups: The next six columns allow the user to enter up to 6 group numbers against each device.
These group numbers are only used for I/O programming.
Map: If a graphical interface is fitted to SmartGraphics this column indicates the Map to which a
particular detector is associated with.