ZONESENSE PLUS
OPERATION & PROGRAMMING
6.3.5 Relays
Press Enter then use the Move Right and / or Move Left keys to select a relay that will be
operated by the selected functions in the sub - menu . Press Enter to access the sub menu then
Move Right and /or Move Left keys to toggle through the sub - menu structure. The sub menu
consists off;
Zone
Alarm
Zone
Fault
Zone
Disable
Input
Switch
Reset
For:
R# Zone
Alarm
R# Zone
Fault
R# Zone
Disable
R# Input
R# Switch
R# Reset
Press Enter then Move Right and /or Move Left keys to select the Zone Alarm / Fault /
Disable, Input or Switch then Enter. Use the Move Right and / or Move Left keys to select the
Zones and the Move Up or Move Down keys to set it to be active or in-active. Active meaning
the Zone Alarm / Fault / Disable, Input or Switch will operate the Relay where as inactive will
prevent them from operating that relay.
RELAY 3
R3 Z . ALM
1...3...5...7...
R2 SWIT
....3...5...7
Press Enter to update the Program and the Cancel to back out to the previous menu.
For:
Reset
Latch
R3 ACFIS
NO
R2 LATCH
YES
R5 RESET
NO
Press Enter then the Move Right and /or Move Left keys to select Reset or Latch then the
Move Up or Move Down keys to set for Yes or No. Yes sets the Relays to be reset or Latched.
Press Enter to update the Program and Cancel to back out to the previous Menu