Page 14
ZONESENSE PLUS
OPERATION & PROGRAMMING
6.2 System
After entering the Level 3 Password and moving to the SYSTEM menu press Enter and the;
1. Zone DISABLED LED’s will illuminate;
Common DISABLED LED will flash; and the
LCD will display;
SYSTEM DISABLED And then BUZZER
Ignoring Buzzer, Mimic and Code menus ( explained below ) use the Move Right or Move Left
keys to move through the menu and the Move Up key to set YES or Move Down key to set
No. Yes meaning the facility / board / card has been fitted to the FACP and will be programmed in
the Programming Menu, No meaning it has not been fitted and will not appear in the Programming
Menu.
Typical Screen examples of the System Menu
6.2.1 Buzzer
This is the only facility in this Menu that has a Sub – Menu. Press Enter to access the Sub – Menu
then theMove Left orMove Right key to select either; Resound, Alarm or XTRA OUTPUT
then Enter. Set the Resound, Alarm by using the Move Up key to Yes (activate on alarm) or
Move Down key for No (not activate on alarm). Set the XTRA OUTPUT option to act as a Reset
or Buzzer function as per the system design configuration.
If the XTRA OUT output is selected set as a Reset or Buzzer function by using the Move Up for
Buzzer or Move Down keys for Reset. Press Enter to update the program.
Resound Set to YES Alarm Set to YES XTRA OUTPUT
6.2.2 Mimic
This tells the FACP how many Zone Mimic Indicator Boards are on the system hence how many to
look for. Set the number by using the Move Down and / or Move Up keys to increment to the
desired number (maximum of 8).