Operators Manual
PAGE 16
DOC No:G0109WO1.doc DIR: L:\MANUALS DATE: 30/11/00 REVISION: 3
6.8.2 Conventional Zone Board
The API-671 Conventional Zone Board provides the interface between the external conventional devices
and the Fi reFinder
TM
Conventional zones are connected from TB4 to TB1 on the API-671 16 Zone Conventional Board.
Fig 6: 16 Zone Conventional Board (API-671)
AZF Parameters
Maximum Line Voltage: The maximum line voltage is limited to the system voltage. With a nominal
battery voltage of 27V, system voltage and therefore open circuit voltage would be approximately 26.4V.
Zone Output Impedance 628 ohms ± 5%
Limits 597 - 660 Ohms
TO CN1 ON
SLAVE CPU
(API669)
TO +27V
REGULATED
POWER
SUPPLY
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 5
ZONE 6
ZONE 7
ZONE 8
ZONE 9
ZONE 10
ZONE 11
ZONE 12
ZONE 13
ZONE 14
ZONE 15
ZONE 16
SERIES 60
DETECTORS
IN STANDARD
BASES