5.2 Expansion Board
The Expansion Connection Board is used to increase the capacity of the controller from 4 Slave
CPU’s to 8. Connection from the Controller to the Expansion Board, which must be mounted within
200mm of the Controller, is made via a 20 way flat cable Slave CPU number 5 is an integral part of
the Expansion Board, only Slave CPU’s 6, 7 and 8 are plug ins. See Figure
Connections
CN1
To Main Connection Board
CN2
To Slave CPU 2
CN3
To Slave CPU 3
CN4
To Slave CPU 4
CN5
On board Slave CPU
302 - 6880 JUN 98
7
6
8
RN5
RN4
C15
U10
C16
C18
C20
C22
C24
C26
C27
C28
U11
U5
RN3
U6
U4
C7
X1
CN5
C5
C6
TP1
R1
RN2
U2
U1
C2
+
C1
CN1
C23
R3
R2
U12
C11
C12
C13
C14
C17
C19
C21
C25
D3
L1
C29
TP2
C10
C8
U8
U7
U9
C9
D1D2
C3
U3
RN1
C4
CN2
CN3
CN4
Slave CPU
Slave CPU
Slave CPU
To CN2 of the
Main Controller
Slave CPU 5
Note: Slave CPU 5 is incorporated
on the Expansion Borad
Slave CPU's 6,7,& 8 all mount onto
the Expansion Board in the same way
as they do to the Main Controller
Figure 22: Board Overlay
5.3 Expansion Controller
An Expansion Controller can be described as a Main Controller without a Front Panel. A maximum of
3 can be introduced into any one Node that is into any one FACP and require a Network Interface
Cards in order to communicate with the Main Board / Controller.
Connecting Controllers together (Networking within the same cabinet) expands the system beyond 8
Slave CPU’s, that is the Main Board plus an Expansion Board.
Networking in this way enables the connection of up to 4 Expansion Controllers within the same
FACP cabinet. This requires the use of NIC’s but offers the added advantage that the RS422
communication bus is internal and all Controllers are physically and logically located at the same
Node. It is now possible to Network up to 32 Slave CPU’s in one cabinet with each Slave CPU
connected to an Addressable Loop, 16 Conventional Zone Board or Digital I/O Board. With this
configuration only one Controller has a Front Panel Board.
Once the system has been expanded to this degree it is obviously quite large and some form of
indication at a point remote from the FACP may become necessary. This is achieved with the use of
a Communications Extender Board for SmartTerminals and/or LED Mimic. Adding a High Level
Interface Board to the Communications Extender Board allows for the addition of HLI, EV3000,
Remote Serial Printer or SmartGraphics facilities.