ADVANCED WARNING
SYSTEMS
Agent Release System AS4214
A FireFinder, LoopSense & ZoneSense PLUS compatible Add-On
PDS4310-0011
PDS4310-0011 Agent Release Module Page 1
WORLD LEADER OF INNOVATIVE SOLUTIONS IN FIRE DETECTION AND ALARM SYSTEMS
Ampac Technologies Australia Tel: +61 8 9201 6100 Europe Tel: +44 (0) 1302 833 522 New Zealand Tel: +64 9 443 8072 www.ampac.net
Product Data Sheet
Controls and Monitors Agent Release System
Outputs for Warning Signs and activation devices
Inputs for signals from pressure switches &
valves
Serial connection to Agent Release Local Control
Station (LCS)
Programmable via the ZoneSense PLUS front
panel.
Programmable via ConfigManager for the
FireFinder range of panels
Programmable via LoopMaster for the LoopSense
(AS7240) range of panels
The Agent Release System comprises of the Main Control
Card, Termination Board and Local Control Stations. In
addition a yellow Manual Call Point can be supplied to fit
to the main Fire Alarm Control Panel (FACP) (This is a
requirement of AS4214 Agent Release Systems)
A maximum of 8 LCS’s can be connected remote to the
panel. An operator may Manually Release or Inhibit
Release from any of these LCS’s
The Agent Release System can be configured to operate
in a single group or dual group mode.
In a single group mode of operation, only one (1) zone
circuit is configured as an ‘agent release’. A detector in
alarm, associated with this type of zone, will initiate a
stage 2 condition. The timer is activated and upon expiry
the agent is released.
In a dual group mode the operator can configure up to
four (4) zones as an ‘agent release’. When a detector in
any zone programmed as an ‘agent release’ goes into
alarm, Stage 1 is activated. Subsequently when a detector
in any other zone that is programmed as an ‘agent
release’ goes into alarm, Stage 2 is activated and the
timer starts. Upon expiration of the timer, the agent is
released.
The Agent Release System supports agents released
using either Metron or a solenoid.
The activation of “Agent Inhibit” switch disables the
automatic release of the agent.