User’s Manual & Log Book
ZoneSense
Page
7
DELAY
ACTIVE
Delay Active - Amber
The indicator is illuminated steady when one or more zones have been configured with a delay,
and the FACP is in the quiescent state.
When the zone that has been configured with a delay reports a fire condition the indicator will
flash (at the fault rate) while the delay timer is running. Once the delay has expired the alarm
outputs and ancillary output are activated and the indicator will extinguish.
The indicator will remain off, until a reset is activated returning the FACP to the normal state.
If the delay override is activated while the delay timer is running then the delay is overridden,
the alarm and ancillary outputs are activated immediately and the indicator will extinguish.
ALARMS
STATUS
Alarms Status - Amber
This indicator is immediately above the Alarms silence / resound switch and indicates a disable
condition (steady) or a fault condition (flashing at the fault rate) on any of the alarm outputs.
Display priority: Disable (steady) then fault (flash)
Zone Indicators
There are two indicators for each alarm zone fitted to the FACP.
Zone Fire – Red
FIRE
ZONE 1 ZONE 2
Individual zone Indicators showing when each zone is in the fire condition (flashing at the alarm
rate) and will become steady when silence resound switch is pressed. An incoming alarm on
another zone will cause that fire indicator to flash while the original indicator will remain steady.
Zone Fault / Disabled / Test – Amber
FAULT / DISABLED / TEST
ZONE 8
ZONE 7
Flashes at the fault rate due to a fault condition on individual zones. Disabling that zone causes
the LED to become steady. Reminder - the disablement has priority over displaying a fault
condition.
Other Indication
The zone indicators are utilised in the disable /enable and walk test process. The following table
summarises the functionality of the zone indicators:
Condition Fire Indicator Fault/Disabled Test Indicator
Alarm (unsilenced) Flashing at the alarm rate -
Alarm (silenced) Steady -
Fault - Flashing at the fault rate
Disabled - Steady (priority over fault)
Normal - -
Disable / Enable Operation
Disable - Rapid Flash
Enable Slow Flash
Walk Test
Selected and under
test
Steady – when the alarm condition
has been detected (3 seconds only)
Rapid Flash
Page view 11