21 Specifications
Mechanical
Dimensions Metal Cabinet: ( mm )
Dimensions ABS Plastic Cabinet: ( mm )
Note: A Battery Box of the same dimension is available
should the FACP be optioned to capacity.
500H x 400W x 140D
300H x 360W x 100D
Environmental
Temperature:
Humidity:
-5ºC to + 55ºC
25% to 75%
Mains Input
Input Voltage:
Protection ( Quick Acting Fuse ):
Minimum Cable Requirements:
90 - 264VAC
1.25 Amp M205
Not less than 0.75mm
Power Supply
Voltage: ( Set to 27.2V )
Power Supply Ripple Voltage:
Power Supply Regulation:
Power Supply Fault Indication Volts High
( at room temperature ) Volts Low
Power Supply Output Current:
Protection:
Batteries / Battery Charger
Charger O/P Voltage:
Battery Type: Sealed Lead Acid
Maximum Battery Capacity:
Maximum Charger Current Limited:
Battery Supply Current Limited:
Battery Discharged Cut-off Voltage:
27.5VDC +/- 0.1VDC
100mV
2%
28VDC
26.5VDC
2Amps
Current Limiting 4Amps
27.5 +/- 0.1VDC
2 x 12V Sealed Lead Acid
7AH
400mA
3A (PTC)
21VDC
Main Card
Quiescent Current ( QI )
QI plus Zone 1 in Alarm
Maximum Current Draw per Output (Current Limited)
40.5mA
90mA
500mA
Zones
Maximum Number of Devices per Conventional Zone:
Cabling Requirements:
Fault monitoring:
32 as per EN54 (40 max)
2 core 1.5 to 2.5mm²
O/C, S/C & EOL
Outputs
Alarm (Current Limited)
Alarm & Fault Monitored Current Limited
Ancillary Alarm & Fault Relay Contacts
Reset / Buzzer
Auxiliary VDC
24VDC @ 500mA Max
24VDC @ 25mA Max
24VDC @ 1A
3sec pulse 100mA @ 24VDC
24VDC 500mA Monitored
Inputs
Class Change, Alert and Spare
0VDC Closing Contact
Communications
Internal to FACP
External to FACP
RS485
RS485
UNCONTROLLED DOCUMENT