Page 9
ZONESENSE PLUS
Chassis Earth Terminal
Earth Cable
Earth Cable
M4 Shake Proof Washer *
M4 Nut *
Note:
* Extra M4 Nut and M4 SPW are
provided finger tight on the Earth bolt.
Figure 10: Chassis Earth Terminal Connection
4.2
Battery Charger
The battery charger is an integral part of the Power Supply and is capable of;
Recharging standard sized system batteries within 24 hours;
Detecting a missing, damaged or undercharged battery;
Protecting the battery against reverse or a short circuit condition;
Charging batteries in line with Sealed Lead Acid battery manufacturerscircuit temperature
compensation guidelines.
Note: Battery disconnect has been incorporated to prevent the battery from discharging
through the battery charger should the charging voltage be less than the battery voltage.
CHASSIS EARTH
TERMINAL
EARTH ( GREEN )
ACTIVE ( BROWN )
NEUTRAL ( BLUE )
NOTE: MAINS CABLE
SHOULD BE NO LESS
THAN 0.75mm
-BATT+
O
F
F
O
N
METAL
COVER
DC OUTPUT
OV +27V GND
1
(AC IN)
1 2 3
TB1
Fuse
B
a
t
t
e
r
y
2
1
2
V
o
l
t
s
B
a
t
t
e
r
y
1
1
2
V
o
l
t
s
+
-
-
+
2
27V TO THE MAIN CARD
A
LED: AC ON
NOTE: 3 AMP
is not fitted with this LED
and uses the Indicator within
the switch
DC ON
LED
DANGER
N
PROTECTIVE PERSPEX
COVER
See Specifications
for correct fuse value
Figure 11: Power Supply Battery Charger Wiring
4.3
Secondary Supply
In the event of a mains failure the backup battery is capable of maintaining the quiescent condition
for 72 hours as well as full alarm load for a further period of 30 minutes.
Note: Any power supply fault to be indicated within 1 hour.