FIREFINDER SERIES II CONFIG MANAGER SESSION 6
12 Network Programming
Single Point Programming FireFinder Series II is the term AMPAC uses to describe the method by
which the network is programmed from one point. It is most important to follow these steps to ensure
trouble free network programming.
12.1 Part 1: Upgrading the Configuration
Before attempting network programming from a single point you should first check the
communications loop and make sure that all panels are operating normally. It is also essential that
all panels on the loop contain a valid configuration and address for the network that they are
connected to. All of the following points refer to commands issued from either a laptop or PC.
It is recommended that all SP programming be carried out from Node 1 (the main panel).
Note: If the panel fails to operate or respond correctly after reprogramming then there are a
number of possibilities as to what has caused the problem. See the troubleshooting section for
remedies.
12.2 State of the Network
Establish the state of the Network and ensure the loop is good using the QP (Query Points)
command:
QP
Bring the entire system back to diagnostic mode to enable the config to be programmed by using the
NGD (Network Go Diagnostic) command: